Current Monitors


Back


Buy Online



FP45S - Single Current Monitor

FP45S - Single Current Monitor


 
 
 
 
 
 
 
 
 
  • Electrical characteristics;
  •    Supply: 230V 50/60 Hz.
  •    Power consumption: < 4VA
  • Functional characteristics;
  •    Adjustable thresholds: 0.1  to 10A AC and DC
  • Measures;
  •    Direct: 0.1 to 10 A~
  •    Via current transformer coil 50/5, 100/5, 150/5,
  •    200/5, 250/5, 300/5, 400/5, 600/5
  • Hysteresis: 5 to 50% of programmed threshold
  • Time delay when exceeding t1 threshold;
  •    t1=0.1 to 12 seconds
  •    t2=0.1 to 20 seconds.
  • Environment;
  •    Operating temperature: -20 to 55C.
  •    Storage temperature: -40 to 70C.
  • Connection capacity;
  •    Flexible: 0.75 to 4mm2
  •    Rigid :1 to 6mm2
  • Enclosure specification;
  •    Protective rating: IP65
  • Insulation class II
  • Colour: Grey RAL 7035 Min.
  • Conforms with EN 50022
  • External Dimensions;
  •    LxHxD (mm) 143 x 210 x 100 Max.

Click here for more information

The Duomo FP45 range of current monitors has been developed to monitor the current drawn by fan motors in ventilation systems. To comply with BS6173:2001 for Commercial Catering Establishments it is necessary to prove that extract and supply air fans are operational before making gas available to the kitchen appliances. The FP45S has two level switching points. Low - to prove that the fan is on and High - to ensure that the motor is drawing the expected load under normal conditions. Some fan motors have a larger load than the FP45S current monitor can tolerate directly (10A max.). In such cases current transformers are used to reduce this current and still allow an accurate indicated value to be displayed on the FP45S.

Product datasheet

Wiring Diagram

[Top]


FP45D - Dual Current Monitor

FP45D - Dual Current Monitor


 
 
 
 
 
 
 

 

  • Electrical Characteristics;
  •    Supply: 230V 50/60 Hz.
  •    Power consumption:<4VA
  • Functional Characteristics;
  •    Adjustable thresholds - 0.1  to 10A AC and DC
  • Measures:
  •    Direct: 0.1 to 10 A~
  •    Via current transformer coil 50/5, 100/5, 150/5,
  •    200/5, 250/5, 300/5, 400/5, 600/5
  • Hysteresis - 5 to 50% of programmed threshold
  • Time delay when exceeding t1 threshold:
  •    t1=0.1 to 12 seconds
  •    t2=0.1 to 20 seconds.
  • Environment;
  •    Operating temperature: -20oC. to 55oC.
  •    Storage temperature: -40oC. to 70oC.
  • Connection capacity;
  •    Flexible 0.75 to 4mm2
  •    Rigid 1 to 6mm2
  • Enclosure Specification;
  •    Protective rating: IP65
  • Insulation Class II
  • Colour: Grey RAL 7035 Min.
  • Conforms with EN 50022
  • External Dimensions;
  •    LxHxD (mm) 143 x 210 x 100 Max.

Click here for more information

The Duomo FP45 range of current monitors has been developed to monitor the current drawn by fan motors in ventilation systems. To comply with BS6173:2001 for Commercial Catering Establishments it is necessary to prove that extract and supply air fans are operational before making gas available to the kitchen appliances. The FP45D has two level switching points. Low - to prove that the fan is on and High - to ensure that the motor is drawing the expected load under normal conditions. Some fan motors have a larger load than the FP45D current monitor can tolerate directly (10A max.). In such cases current transformers are used to reduce this current and still allow an accurate indicated value to be displayed on the FP45D.

Product datasheet

Wiring Diagram

[Top]


FPCTC - Current Transformer

FPCTC - Current Transformer


 
  
 
 
 
 

 

  • Secondary current: 5A
  • Maximum voltage rating Ue: 720V
  • Frequency: 50 - 60Hz
  • Permanent permissible overload: 1.2 In
  • Safety factor;
  •   40 to 4000A primary: Fs<5
  •   5000, 6000A primary: Fs<10
  • IP20
  • Ambient installation temperature;
  •   Standard range: -50 to 55C
  •   Tropicalised range: -25 to 60C
  • Relative humidity;
  •   Standard range: <95%
  •   Tropicalised range: >95%
  • Standards;
  •   Watt-hour meters: BSEN61036, IEC61036
  •   (with sealable cover)
  •   Current transformers: BS7626, IEC44-1

Click here for more information

Some fan motors have a larger load than the FP45 current monitor can tolerate directly (10A max.). In such cases the FPCTC current transformer is used to reduce this current and still allow an accurate indicated value to be displayed on the FP45.

Product datasheet

[Top]