Estro B2 - Flame Controlling Device

Estro B2 - Flame Controlling Device


 
 
 
 
 
 
 
 
  • Supply voltage: 115 or 230 V +10-15%
  • Frequency: 45 - 65 Hz
  • Power consumption (without outlets): 4 VA max
  • Operating temperature: 0 - 60°C
  • Storage temperature: -20 - 80°C
  • Maximum relative humidity: 75 %
  • Protection class (when wiring, use adequate connectors): IP54
  • Mounting position: any
  • Load protection fuse: 3.15 A
  • Device protection fuse: 1 A
  • Maximum output capacity: 3 A @ 230 V cosj = 0.5
  • Probe voltage: 300 V ac
  • Minimum ionization current: 3 mA
  • Flame current limitation: 3,2 mA
  • Flame signal display: 0 - 90 mA
  • Prepurge time: 0 - 255 s
  • First safety time: 1 - 25 s
  • Main burner stabilization time: 1 - 25 s
  • Reaction time: 1 - 20 s
  • Post-purge time: 0 - 255 s
  • Auto shutoff (can be inhibited): within 24 hours
  • Optional inputs voltage: 24, 48, 115, 230 V ac/dc
  • Optional inputs absorption: max 5mA (thermostat, pressure switch, limit switch)
  • Lock/reset input absorption: max 5mA
  • Filter for lock/reset input: RC 100W - 0.47 mF - 250 V ac
  • Casing: thermosetting
  • Dimensions: 200×120×93 mm
  • Mass: 1.200 g
  • Flame controlling device: rod or UV-2 phototube (ESA)
  • Insulation among probe conductors: > 50 MW (double-insulation or double-protection cables)
  • Rod or UV tube probe line length: < 30 m
  • Unirod probe line length with TAR-10 transformer: 2 m max

Click here for more information

ESA Estro is a microprocessor-operated flame controlling device equipped with inputs and outputs for the ignition and control of industrial burners. Estro B2 is a device for two-stage burners (pilot and main gas valves). Remote control via electric and serial signals with powered output when the burner is on.

Product datasheet

Order form

[Top]


Estro C2 - Flame Controlling Device

Estro C2 - Flame Controlling Device


 
 
 
 
 
 
 
 
  • Supply voltage: 115 or 230 V +10-15%
  • Frequency: 45 - 65 Hz
  • Power consumption (without outlets): 4 VA max
  • Operating temperature: 0 - 60 °C
  • Storage temperature: -20 - 80 °C
  • Maximum relative humidity: 75 %
  • Protection class (when wiring, use adequate connectors): IP54
  • Mounting position: any
  • Load protection fuse: 3,15 A
  • Device protection fuse: 1 A
  • Maximum output capacity: 3 A @ 230 V cosj = 0.5
  • Probe voltage: 300 V ac
  • Minimum ionization current: 3 mA
  • Flame current limitation: 3,2 mA
  • Flame signal display: 0 - 90 mA
  • Prepurge time: 0 - 255 s
  • First safety time: 1 - 25 s
  • Main burner stabilization time: 1 - 25 s
  • Reaction time: 1 - 20 s
  • Post-purge time: 0 - 255 s
  • Auto shutoff (can be inhibited): within 24 hours
  • Optional inputs voltage: 24, 48, 115, 230 V ac/dc
  • Optional inputs absorption: max 5mA (thermostat, pressure switch, limit switch)
  • Lock/reset input absorption: max 5mA
  • Filter for lock/reset input: RC 100W - 0.47 mF - 250 V ac
  • Casing: thermosetting
  • Dimensions: 200×120×93 mm
  • Mass: 1.200 g
  • Flame controlling device: rod or UV-2 phototube (ESA)
  • Insulation among probe conductors: > 50 MW (double-insulation or double-protection cables)
  • Rod or UV tube probe line length: < 30 m
  • Unirod probe line length with TAR-10 transformer: 2 m max

Click here for more information

ESA Estro is a microprocessor-operated flame controlling device equipped with inputs and outputs for the ignition and control of industrial burners. Estro C2 is a device for one-stage burners (only one gas valve). Remote control via electric and serial signals with normally open output when the burner is on.

Product datasheet

Order form

[Top]


Estro Q2 - Flame Controlling Device

Estro Q2 - Flame Controlling Device


 
 
 
 
 
 
 
 
  • Supply voltage: 115 or 230 V +10-15%
  • Frequency: 45 - 65 Hz
  • Power consumption (without outlets): 4 VA max
  • Operating temperature: 0 - 60 °C
  • Storage temperature: -20 - 80 °C
  • Maximum relative humidity: 75 %
  • Protection class (when wiring, use adequate connectors): IP54
  • Mounting position: any
  • Load protection fuse: 3,15 A
  • Device protection fuse: 1 A
  • Maximum output capacity: 3 A @ 230 V cosj = 0.5
  • Probe voltage: 300 V ac
  • Minimum ionization current: 3 mA
  • Flame current limitation: 3,2 mA
  • Flame signal display: 0 - 90 mA
  • Prepurge time: 0 - 255 s
  • First safety time: 1 - 25 s
  • Main burner stabilization time: 1 - 25 s
  • Reaction time: 1 - 20 s
  • Post-purge time: 0 - 255 s
  • Auto shutoff (can be inhibited): within 24 hours
  • Optional inputs voltage: 24, 48, 115, 230 V ac/dc
  • Optional inputs absorption: max 5mA (thermostat, pressure switch, limit switch)
  • Lock/reset input absorption: max 5mA
  • Filter for lock/reset input - RC 100W - 0.47 mF - 250 V ac
  • Casing: thermosetting
  • Dimensions: 200 x 120 x 93 mm
  • Mass: 1.200 g
  • Flame controlling device: rod or UV-2 phototube (ESA)
  • Insulation among probe conductors: > 50 MW (double-insulation or double-protection cables)
  • Rod or UV tube probe line length: < 30 m
  • Unirod probe line length with TAR-10 transformer: 2 m max

Click here for more information

ESA Estro is a microprocessor-operated flame controlling device equipped with inputs and outputs for the ignition and control of industrial burners. Estro Q2 is a device for one-stage burners (only one gas valve). Remote control via serial signals.

Product datasheet

Order form

[Top]


Reflam - Flame Presence Indicator

Reflam - Flame Presence Indicator


 
 
 
 
 
 
  
 
  • Supply voltage: 115 or 230 V +10-15%
  • Supply frequency: 45 - 65 Hz
  • Max absorption: 4 VA max
  • Operating temperature: 0 - 60°C
  • Storage temperature: -20 - 80°C
  • Maximum relative humidity: 75 %
  • Mounting position: any
  • Protection degree: IP54 (when wiring use adequate cable gland)
  • Atmospheres: not suitable for use in explosive or corrosive atmospheres
  • Casing: thermosetting
  • Dimension: 200 x 120 x 93 mm
  • Weight: 1200 g
  • Ignition transformer protection fuse: 3,15 A
  • Device protection fuse: 1 A
  • Maximum output capacity: 3 A @ 230 V cosϕ= 0,5
  • Ignition time: 1 - 25 s
  • Flame failure response time: 1 - 9 s
  • Remote start input absorption: max 5mA
  • Filter for remote start input - RC 100Ω - 0,47 μF - 250 Vac
  • Probe voltage: max 300 Vac
  • Minimum ionisation current: 3 μA
  • Flame current limitation: 3,2 mA
  • Flame signal display: 0 - 90 μA
  • Flame controlling devices: rod or ESA UV-2 phototube
  • Insulation among probe conductors: > 50 MΩ (double-insulation or double-protection cables)
  • Rod or UV tube line length: max 30 m
  • Unirod probe line length with TAR-10 transformer: max 2 m

Click here for more information

Reflam is a microprocessor-based flame presence indicator with outputs and inputs to control and signal flame presence for multi-nozzle burners or all applications where the fuel cannot be directly controlled and where flame controls cannot be used. The instrument is used for remote signalling via two voltage-free outputs. In addition, for multi-nozzle or multiflame burners, the presence of an illegal flame can be monitored and the ignition transformer can be remotely controlled by means of the start input. Note that in these applications the solenoid valves for fuel interception must be controlled by certified flame control devices (see EN-746/2). ESA Reflam is equipped with an ECS serial interface that enables the ignition transformer to be activated and flame presence to be monitored remotely, permitting the control of several instruments by means of the serial communication. A local Start/Stop pushbutton is found on the front panel, together with a display showing the cycle, a bar graph flame signal indicator and two LEDs for configuration of the serial address using infrared. The instrument also makes a Start/Stop input available for remote control. ESA Reflam is supplied in a robust thermosetting casing designed for housing the TAR-10 ignition transformer and for the cable outlets, that can be pre-wired on request. ESA Reflam permits the parameters and modes of operation to be configured according to the requirements of the application using dedicated programming software.

Product datasheet

Order form

[Top]


Genio - Flame Controlling Device

Genio - Flame Controlling Device


 
 
 
 
 
 
 
 
  • Supply voltage: 115/230 Vac
  • Frequency: 45 - 65 Hz
  • Power consumption (without outlets): 10 VA max
  • Operating temperature: 0 - 60°C
  • Storage temperature: -20 - 80°C
  • Protection fuse: 3,15 A
  • Maximum output capacity: 3A @ 230 V cos Q = 0,5
  • Probe voltage: 280Vac
  • Minimum ionization current: 3 μA
  • Flame current limitation: 1mA
  • Prepurge time: 0 - 65 sec (5 sec. multiple)
  • First safety time: 3-5-7-10 sec
  • Reaction time: 1 sec
  • Resistance for burner counting device: 1.8 KΩ ¼ W 1%
  • Casing: thermoplastic
  • Dimensions: 200 x 120 x 93 mm
  • Protection class: IP40
  • Mass: 1.200 g
  • Mounting position: arbitrary
  • Flame controlling device: flame rod or unirod
  • Rod line length: < 2mt

Click here for more information

ESA Genio is a microprocessor-operated flame controlling device designed to supervise one-stage burners, displaying the status of the burner in an extremely simple though thourough way. The device is description supplied with a strong thermoplastic casing equipped with holes for cable outputs which may be cabled in advance if required and for the ignition transformer. On the front panel there is an on/off button, a reset button and three LED's for general information about power supply, status of the burner and lock out status. The device warns the controlling system if there is any burner failure in the burner either by closing the normally open contact or displaying no defaults in the burner via an output with a calibrated resistance to connect to a burner counting device. ESA Genio allows to change both the prepurge time and recycle even during the installation phase, whereas safety and reaction times are fixed and may only be modified by the producer.

Product datasheet

Order form

[Top]


UV2 - Flame Sensor

UV2 - Flame Sensor


 
 
 
 
 
 
  
 
  • Spectral response: 185 - 260 nm
  • Peepsight connection: ¨ 3/4” gas
  • Discharge starting voltage (with UV radiation): 280V
  • Recommended oper. voltage: 325 ±25V
  • Max. voltage: 400V
  • Recommended discharge current: 100μA
  • Average discharge current (note A): 1mA
  • Max. peak current (note B): 30mA
  • Operating temperature: -20 - 60°C
  • Background (note C): max. 10 cpm
  • Sensibility (note D): 5,000 cpm (> 1pW)
  • Life service with continuous discharge: > 10,000 hours 

Click here for more information

The UV2 Flame Sensor is a flame detector for industrial use installed in a robust, die-cast aluminium box equipped with plug-in connection and threaded connection for the peepsight. It contains a gas filled UV tube. UV-rays (not daylight or artificial light from discharge or filament lamps) ionise the gas in the tube.

Product datasheet

[Top]


ECS Driver - Serial Communication Interface for Estro Devices

ECS Driver - Serial Communication Interface for Estro Devices


 
 
 
 
 
 
 
 
  • Supply voltage: 90 - 240vac
  • Supply frequency: 40 - 70 Hz
  • Max. absorbtion: 40W
  • Operating temperature: 0 - 50°C
  • Storage temperature: -10 - 70°C
  • Fixing: on 35 mm DIN guide (EN50022)
  • Mounting position: any
  • Dimensions ECS-DRIVER-S:  75 x 125 x 80mm high
  • Dimensions ECS-DRIVER-D: 260 x125 x 80mm high
  • Weight ECS-DRIVER-S: 600 g
  • Weight ECS-DRIVER-D: 750 g
  • Protection degree: IP10
  • Atmospheres: not suitable for use in explosive or corrosive atmospheres
  • Fieldbus voltage: 25Vdc max.
  • Data transmission speed: 9600 baud max.
  • Length ECS line: 200 m max. wih ECS cable or busway
  • Units connectable to active output 4800 baud 70 max.; 9600 baud 60 max.

Click here for more information

ECS Driver is an interface card allowing any controlling device to communicate with units equipped with ECS (Esa Communication System) serial input. The ECS bus guarantees good immunity to electromagnetic disturbances, using high electrical signal levels and medium communication speed. It entails the parallel connection of all units and the simultaneous use of busways and cables with the additional advntage of connecting and disconnecting units without having to close the communication loop. The ECS bus entails a master-slave type communication with only one active interface for each section of the serial line. If the application finds a number of units exceeding the number the ECS active output is designed for, it is possible to use ECS Driver as a signal repeator. The ECS signal to the bus is taken at the active output. The ECS Driver is equipped with connection for DIN guide to be installed in electrical panels, located near the master controller or on the equipment. The ECS Driver has two LED's to indicate the data flow sense on the serial line: one LED lights when the interface is transmitting, whereas the second one lights when the interface is receiving.

Product datasheet

[Top]


Prog-1 - Handheld Programmer for Estro Devices

Prog-1 - Handheld Programmer for Estro Devices


 
 
 
 
 
 
 
 
  • Supply voltage 9V dc from battery programmed to automatically disconnect after 5 minutes
  • Low battery signal Lob
  • Operating temperature: 5÷45°C
  • Storage temperature: 0÷60°C
  • Electrical protection: IP40
  • Maximum dimensions 145 x 85 x 39 mm
  • Weight 250 g
  • Serial interface infrared or ECS (double-wire)
  • Distance with infrared interface 100 mm max from device
  • Distance with ECS interface 1 m max from device
  • Baud rate 4800
  • Data bits 8
  • Parity none
  • Stop bits 1 or 2
  • Communication line voltage (ECS) 25 Vdc max
  • Connectable units max 1

Click here for more information

Prog-1 is a device designed to program the communication parameters of the flame control devices of the ESTRO series and of the previous devices. The configuration may be carried out either via serial line (ECS) or infrared signals. Due to its small size and the fact it has no supply cable the device is easy to handle and use. The front panel has 5 buttons for the selection and transmission of the parameters and an LCD for data display; the infrared interface is on the front, whereas the connector for the ECS connection (double wire) is on the side. When the device is switched on, it displays the serial address (segment and node) which may be modified and transmitted to the flame control. The choice of the type of interface is to be done during the ″Programming″ mode. The device displays the sequence of the operations it is carrying out, and also any possible communication errors.

Product datasheet

[Top]